PART 1 - GENERAL

1.01 Work Included:
Edit acoustical where required
  1. Sprayed cellulose thermal [and acoustical] insulation..

1.02 Related Items:
  1. Clips, hangers, supports, sleeves and other attachments to spray bases are to be placed by other trades prior to the application of sprayed insulation.
  2. Ducts, piping, conduit or other suspended equipment shall not be positioned until after the application of sprayed insulation.
  3. Roof penetrations to be installed prior to application.

1.03 Quality Assurance:
  1. Manufacturer must be ISO 9001:2000 Certified.
  2. Applicator: Licensed by manufacturer.
  3. Manufacturer must subscribe to independent laboratory follow-up inspection services of Underwriters Laboratories and Factory Mutual. Each bag shall be labeled accordingly.
  4. Mock up: Apply a 100 square foot representative sample to be reviewed by the Architect and/or Owner prior to proceeding.

1.04 Submittals:
  1. Submit product data and manufacturer's certificate that the product meets or exceeds specified requirements.
  2. Manufacturer's written certification that product contains no asbestos, fiberglass or other man made mineral fibers.
  3. Copy of manufacturer's ISO 9001:2000 Certification.

1.05 Product Delivery, Storage and Handling:
  1. Deliver in original, unopened containers bearing name of manufacturer, product identification and reference to U.L. testing.
  2. Store materials dry, off ground, and under cover.
  3. Protect liquid adhesive from freezing.

PART 2 - PRODUCTS

2.01 Acceptable Manufacturers:
  1. International Cellulose Corporation
    12315 Robin Boulevard
    Houston, Texas 77045
    (713) 433-6701 or (800) 444-1252
    FAX: (713) 433-2029

  2. For approved applicators contact ICC at 800-444-1252.

2.02 Materials:
  1. K-13 Spray-On-Systems.
    1. Color shall be as indicated in Schedule 3.05.[Color selection will affect price]
    2. Apply at minimum thickness to provide an R-value(s) as indicated in Schedule 3.05. [Add Thermal Resistance values if applicable]
    3. Comply with ASTM E-736 for field-tested bond strength; tested @ > 5 years.
      1. Not less than 400 psf
      2. Not less than 600 times its weight @ 1"
    4. Comply with ASTM E-84/U.L. 723, Tested at a minimum of 5" thickness Class 1, Class A

      Flame Spread 5
      Smoke Development 5

    5. Comply with local Building Code requirements.
    6. Comply with ASTM E-1042.
    7. NRC Rating [Edit NRC rating if applicable]:
      Install at a minimum thickness to achieve a NRC rating as indicated in the Schedule 3.03

      Inches 125HZ 250HZ 500HZ 1000HZ 2000HZ 4000HZ NRC
      K-13 Sprayed Thermal and Acoustical Insulation ASTM C-423 on Solid Backing*
      1.00" .08 .29 .75 .98 .93 .96 .75
      1.00** .47 .90 1.10 1.03 1.05 1.03 1.00
      2.00" .26 .68 1.05 1.10 1.03 .98 .95
      3.00 .57 .99 1.04 1.03 1.00 1.00 1.00

      Some values interpolated **On lath

      Inches 125HZ 250HZ 500HZ 1000HZ 2000HZ 4000HZ NRC
      K-13 Sprayed Thermal and Acoustical Insulation Applied at 1.5" Ribbed Metal Deck*
      1.5 .36 .89 1.26 1.07 1.01 1.00 1.05
      3.00" .97 1.04 1.13 .99 .95 .98 1.05

      Some values interpolated **On lath

    8. Non corrosive per ASTM C 739.
    9. Bond Deflection per ASTM E-759: 6" Deflection in 10' Span - No Spalling or Delamination
    10. Cohesive Strength at time of application per Method WS-2000: > 700 Grams
PART 3 - EXECUTION
3.01 Examination
  1. Examine surfaces and report unsatisfactory conditions in writing. Do not proceed until unsatisfactory conditions are corrected.
  2. Verify surfaces to receive spray insulation to determine if priming/sealing is required to insure bonding and/or to prevent discoloration caused by migratory stains.
3.02 Preparation
  1. Provide masking, drop cloths or other satisfactory coverings for materials/surfaces that are not to receive insulation to protect from over-spray.
  2. Coordinate installation of the sprayed cellulose fiber with work of other trades.
  3. Prime surfaces as required by manufacturer's instructions or as determined by examination.
3.03 Installation
  1. Thickness will be determined as the minimum thickness measured as per ASTM E-605 field test procedure.
  2. Install spray applied insulation according to manufacturerÕs recommendations
  3. Cure insulation with continuous natural or mechanical ventilation.
  4. Remove and dispose of over-spray.
3.04 Protection
  1. Protect finished installation under provision of Division 1
3.05 Schedule
Provide a schedule when insulation requires listing by color, insulation value, NRC values and attributes.